Flex TPO Enhanced Wind Uplift Manual de usuario Pagina 3

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 3
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 2
8/2012 3
b) 1/4 DensDeck Prime 12 fasteners per 4x 8 board.
c) 1/4" Securock Gypsum-Fiber 12 fasteners per 4x 8 board.
2) Wind Speeds to 90 mph.
a) Polyisocyanurate Insulation Board (25 psi Min 1 ½ thick) 16 fasteners per 4x 8 board.
b) 1/2 DensDeck Prime 12 fasteners per 4x 8 board.
c) 1/2" Securock Gypsum-Fiber 12 fasteners per 4x 8 board.
3) Wind Speeds to 100 mph.
a) 7/16 OSB over Flex ISO board. 17 Fasteners per 4x 8 board.
b) 5/8 DensDeck Prime 16 fasteners per 4x 8 board.
c) 5/8 Securock Gypsum-Fiber 16 fasteners per 4x 8 board.
4) Wind Speeds to 120 mph.
a) 7/16 OSB over Flex ISO board. 17 Fasteners per 4x 8 board.
b) 5/8 DensDeck Prime 24 fasteners per 4x 8board.
c) 5/8 Securock Gypsum-Fiber 24 fasteners per 4x 8 board.
Note: Fastener to be Flex Standard Insulation fastener with 3 metal insulation plate. Fastener density
listed above is for field of roof area. Fastener density must be increased a minimum of 60% in the roof
corner areas and 40% in the roof perimeter area.
Vista de pagina 2
1 2 3

Comentarios a estos manuales

Sin comentarios